Supplement your ventilation with equivalent air changes

In May 2023 the NHS issued NETB 2023/01a, an addendum to HTM 03-01, setting out how local HEPA filter air cleaners can supplement ventilation in poorly and naturally ventilated spaces.

Equivalent air changes per hour (eACH).A room running at 6 ACH can reach the equivalent of 10 ACH by adding a unit that provides 4 eACH, on top of your existing ventilation. The guidance is clear that air cleaners supplement ventilation, they are never a reason to reduce it.

✓ H13 HEPA filtration to BS EN 1822-1, at least a 99% single-pass reduction

✓ Published clean air delivery rate for every fan speed, so the eACH is backed by data

✓ Meets the sound pressure levels the guidance sets for occupied areas, with a filter-change indicator and CE/UKCA marking

Why the IQAir Cleanroom H13

  • Meets the spec

    H13 HEPA to BS EN 1822-1 with published CADR at every fan speed, the operational criteria NETB 2023/01a sets out.

  • No works needed

    Free-standing units on a standard 13-amp socket. Add air changes and leave your existing ventilation as it is.

  • Built for wards

    Designed to run in occupied spaces, with a filter-change indicator so the team knows when service is due.

Published clean air delivery rate

Real airflow at each of the Cleanroom H13's six fan speeds, so we can calculate the equivalent air changes it adds to a room of known volume.

Fan speed Clean air delivery rate (m³/h)
Speed 1 65
Speed 2 120
Speed 3 190
Speed 4 270
Speed 5 370
Speed 6 530

Backed by peer-reviewed evidence

IQAir's filtration is supported by published research in real healthcare settings, something very few air cleaning manufacturers can point to.

50% fewer aspergillosis infections.A study in the American Journal of Infection Control found portable IQAir HEPA units halved the rate of invasive aspergillosis. With each case adding around 12 days in hospital and over $50,000 in cost, the researchers judged portable HEPA a highly cost-effective control measure.

Up to 93% less environmental MRSA.At Nottingham City Hospital, published in the Journal of Hospital Infection, IQAir units cut environmental MRSA contamination in patient rooms by 75 to 93%, lowe